How to Mark a Custom Transition or Offset on a Sketch
Some fittings never make it onto a clean schedule line. A transition that has to clear a beam or an offset that drops around a pipe rack usually shows up as a field sketch or a markup on a plan sheet. The sketch is often the fastest way to explain the piece. It is also where most custom fitting questions come from, because a sketch that is obvious to the person who measured it can be read more than one way back at the shop.
This article covers how to mark a custom transition or offset on a sketch so it can be priced and fabricated without a call-back: what to show, which way the piece faces, which sides stay flat, and how to send it.
For the full quote checklist (drawings, materials, connections, releases, pickup or delivery), see the Contractor Guide. For custom fittings as a product - transitions, offsets, and equipment connections fabricated from your drawings - see Custom Duct Fittings. This post stays on the sketch only.
DuctAxis is a commercial duct fabricator in Clewiston, Florida. We fabricate. We do not install.
Why sketches get sent back
A sketch is a drawing of a three-dimensional piece on a flat page. That is where the trouble starts. Two numbers written next to an opening could be width x height or height x width. An arrow could mean airflow or could mean "this way to the unit." A line drawn straight across the top could mean that side is flat, or it could just be the way the pencil went.
Common gaps on custom fitting sketches:
- Only one opening is dimensioned
- Width and height are written in a different order than the rest of the set
- No length between the two openings
- No offset distance, or no direction for the offset
- No note on which sides stay flat or flush
A sketch with the notes below is enough to start estimating.
Start with the mark and the view
Before any dimensions, put two things on the page.
The mark. Write the fitting mark or tag that matches the plan, or the drawing sheet and location if the piece has no mark yet. If one sketch covers more than one identical piece, write the quantity next to the mark.
The view. Label what the drawing shows: top view (plan), side view (elevation), or end view. If you draw more than one view of the same piece, label each one. A transition drawn only from the top hides anything that happens in the height. When the piece changes in both directions, draw two views.
Dimension both openings
A transition or offset is defined by the two ends. Dimension both, every time, even when they look the same.
Entering opening
- Size as width x height for rectangular, or diameter for round
- Which dimension is the width and which is the height, labeled on the drawing (write "W" and "H," not just two numbers)
Leaving opening
- Size in the same order and format as the entering opening
- The shape, if it changes (for example, rectangular to round)
Use the same width x height order that the rest of your set uses. If the set lists width first, the sketch should too. If the duct is lined or double-wall, say whether the sizes are inside (clear opening) or outside.
Show which way it faces
Facing is the part a sketch most often leaves out, and the part that is hardest to fix after the piece is built.
- Airflow. Draw one arrow for airflow and label it "airflow." Do not use plain arrows for anything else on the page.
- Up and down. On a side view, mark which side is top. On a top view, mark which side is toward a wall, column, or other fixed point.
- Reference points. If the piece has to meet something - a unit opening, a wall, a slab, a beam - name it on the sketch ("this side to RTU-2," "bottom flush to slab").
A short written note next to the drawing is fine, and it is clearer than an unlabeled arrow. Use one unit throughout, and write "not to scale" if the proportions are off - the numbers matter more than the drawing.
Mark the flat sides
On a transition, the change in size has to come from somewhere. The shop needs to know which sides stay straight and which sides slope.
- Concentric: all sides taper toward the center line.
- Flat on one side: for example, "top flat" or "bottom flat," when one face has to stay in line with a slab, ceiling, or the next run.
- Flat on two sides: for example, "top and one side flat," when the piece sits in a corner or against two surfaces.
Write the flat side on the drawing itself, not only in a note at the bottom of the page. If the sketch shows one side as a straight line on purpose, label it "flat." If it does not matter which sides taper, say that too ("flat side not critical") so the shop does not have to ask.
Give the offset distance and the length
An offset moves the duct centerline. A sketch needs to show how far and over what length.
- Offset distance. How far the centerline moves. If the piece offsets in two directions, give both (for example, "up 6 in., right 4 in.").
- Direction. Up, down, left, or right, as seen in the labeled view, with airflow marked.
- Length. The length of the fitting along the duct run, or the space you have between fixed points if the length has to fit a gap.
If the space is tight, write the available length and what you are working around. That is more useful than a length rounded to look neat.
When a piece is both a transition and an offset, mark it as both: two openings, the flat sides, the offset distance and direction, and the length.
Note the ends and the construction
Each opening on a custom fitting connects to something. Note what the drawings or specs call for at each end:
- Connection at each end, if it differs from the run or is called out at equipment
- Material and construction as shown on the documents (bare, lined, double-wall, and so on)
- Anything the spec requires, such as an access door or a test port, when the documents show it on that piece
Do not invent a gauge or a connection type on the sketch. Send what the drawings or specs state. If the documents do not say, leave it open and flag it, and it can be confirmed during estimating.
Quick checklist before you send the sketch
If a box is empty, either fill it in or flag it in the request ("flat side to be confirmed in field before release"). That is faster than a sketch that looks complete and is not.
How this fits the custom fittings page
The Custom Duct Fittings page is where custom fitting work lives: transitions, offsets, and equipment connections fabricated from your drawings, fitting schedules, and dimensions. This article does not replace that page; it only explains how to mark a sketch so those pieces arrive with the notes the shop needs.
When you are ready to price the package, use the Contractor Guide for project details, drawings, construction requirements, dates, and pickup or delivery notes.
Send your sketch with the request
When the sketch is marked, scan or save it as a legible PDF and request a quote. Uploads accept PDF, XLSX, XLS, CSV or ZIP files: up to 8 files, 20 MB each, 50 MB total. For a larger package, call (863) 599-7014 or email office@ductaxis.com.
- Quote response time: under 48 hours, excluding weekends. That is how long it takes to get a quote back, not the fabrication lead time.
- Shipping: Free shipping anywhere in Florida. Delivery outside Florida is confirmed with your quote.
- Shop: 535 E El Paso Avenue, Suite C, Clewiston, FL 33440
Free estimates from your mechanical plans (PDF). Send what you have; clear openings, facing, and flat-side notes still make the first pass cleaner.
Final dimensions, materials, and fabrication follow your approved project requirements and are confirmed during estimating. This article is general guidance for marking custom fitting sketches and does not replace your project specifications, drawings, or engineer of record.
Request a quote